The TEIP11 signal converter converts electrical standard
signals, e.g. 4 … 20 mA to 0.2 … 1 bar (3 ... 15 psi). It is
therefore a connecting link between electrical/electronic and
pneumatic systems. The signal conversion process is similar
to the patented force balance method.
Special features of the TEIP11 signal converter are its relatively
small dimensions and outstanding operational stability when
subject to shock and vibration. The converter can be
subjected to loads up to 10 g with less than 1% effect on
function.
The housing units are available in a variety of models to meet
your installation requirements. For potentially explosive
conditions, units that offer intrinsically safe operation or
pressure-resistant encapsulation are available with
international approval certificates for use worldwide.
Specifications
Input (electric)
Signal range
0 ... 20 mA or 4 ... 20 mA
0 ... 10 mA or 10 ... 20 mA
4 ... 12 mA or 12 ... 20 mA
(additional ranges available upon request)
Input resistance
Ri = 260 Ω at 20 °C (68 °F), Tk + 0.4 %/K
Overload limit
30 mA (for explosion-proof devices, see the information in
chapter "Ex relevant specifications" on page 5)
Capacitance/inductance
Negligible
Output (pneumatic)
Signal range